Rd SKE 2 smokeproof sliding door

Characteristics
- Double leaf
- Full leaf in modular element design
- Leaf and frame profiles galvanized
- General building code test certificates
- P-BWU 03-I 17.67.17 for double leaf T30 version
- P-BWU 03-I 17.67.34 for double leaf T90 version
Versions
- Smokeproof in accordance with DIN 18095 Part 3
- With door ingoing brake (radial damper)
- Also available with hold-open system
- Also available for low headers, with optional inlet and/or header panel
- Also available with activation aids
- Also available with panel field glazing
Standard pane size 270 x 630 mm,
special pane sizes up to 450 x 1100 mm (longer lead times),
requisite frieze width per panel field 190 mm on three sides,
pedestal height 1150 mm. - Also available with smokeproof pass door
(for single leaf doors only, can be combined with T30 or T90 fire protection)
Smallest dimensions with pass door 1675 x 2100 mm CP - Also available with T30 or T90 in accordance with DIN 4102
(see previous double page)
Description
Approved dimensions
Height: max. 4500 mm
Width: max. 7000 mm
Single leaf doors up to approx. 25 m² CP
Single leaf doors with movable central joint up to approx. 15 m²
Double leaf doors up to approx. 15 m² CP
- Sliding door leaves up to 1500 mm in width must not be
higher than max. 2500 mm (CP in each case).
Door leaf
Thickness: approx. 67 mm
Sheet metal: 1 mm
Weight: approx. 55 kg/m²
Door leaf must overlap the clear opening:
by ≥ 70 mm at the sides
with T30 ≥ 100 mm
with T90 ≥ 150 mm by ≥ 75 mm at the header
(by ≥ 85 mm in the case of low headers)
Note: The upper horizontal smoke seal protrudes about 30 mm into the clear passage.
Storage area for opened door
= Clear opening width + 350 mm
(plus additional 150 mm for low headers with closing weight an inlet)
Necessary header height (mm) for
normal header/wall installation ≥ 220
low header/ceiling installation ≥ 125
Wall clearance
≥ 200 mm
Sill for opening and storage area
recessed or surface mounted on the floor, or optionally without if the site has been prepared accordingly.
- On-site preparation if the sill is recessed in the floor. Floor sill is set with sill brackets, aligned and filled (on-site) prior to installation of the door.
- Evenness tolerance for finished floors with mounted sill in the opening and storage area in accordance with DIN 18202, Table 3, Line 4.
- A floor sill is not necessary if the floor is smooth and even, and without joints in the opening and storage area.
Additional features
Smokeproof pass door 1000 x 2000 mm without sill, for single leaf smokeproof sliding doors only (Rd SKE 1), can be combined with T30 or T90 fire protection. Smallest dimensions with pass door 1675 x 2100 mm CP.
Activation aids and special features on request

Activation aids and
special features on request

Activation aids and
special features on request

Clear passage width
(*)
door without pass door 200 mm
door with pass door 250 mm
door with bag flap 280 mm
All dimensions in mm
CP = Clear passage dimensions
UEFF = Upper-edge finished floor
See page 5 for hardware and other optional features,
see pages 10/11 for planning and installation notes